Skip navigation


Intrinsically Safe Detectors

Conventional (SUO601)

The Tyco Manual Call Point (MCP) is a surface mounting call point with a plastic coated glass element to ensure reliable, safe operation. The Tyco MCP’s are available coloured Red or White. Note that for Red coloured devices, it is necessary to order both the MCP and the Wall Box.

The call point is operated by snapping the glass element by pressing on its centre – a hammer, or other impact device, is not required. The snapped glass element releases the MCP’s micro switch, which signals an alarm to the fire panel.

Technical Data Sheet
Brochure
SSL Approval


SU0600 15V Manual Call Point

The SU0600 15V Manual Call Point (MCP) clamps the line voltage to 15 volts when actuated. When used on the same circuit as collective fire detectors, it complies with AS1670.1 by not extinguishing the LED indicator of an already activated fire detector. This MCP has a plastic coated frangible element to ensure safe and reliable operation, producing no dangerous glass shards. The MCP is operated by simply pressing on the centre of the frangible element until it snaps. This releases the MCP’s micro switch, which signals an alarm at the FIP and illuminates the integral LED indicator. The unit features IN and OUT terminals, which are requirements of AS1670.1 and is compatible with the MX4428 ADR-M, F3200 (band 3 Instant Alarm) and F08 version 3.

Specifications

  • Operating Voltage 18 to 28Vdc
  • Quiescent Current 5μA max. @ 24Vdc
  • Alarm Current* 30mA max.
  • Alarm Current 1mA max @ 8Vdc
  • Alarm Voltage 14 to 16Vdc
  • Reverse Polarity Current 100mA max.
  • Reverse Polarity Voltage 0 to 1Vdc
  • Ambient Temp -10 to +70°C Indoor only
  • Relative Humidity 10% to 95% (non cond.)
  • CSIRO ActivFire Listed afp-1385

Part Numbers

  • SU0600 15V MCP (excl. backbox)
  • SU0632 Red Backbox
  • SU0615 Transparent Hinged Cover
  • 515.001.025 Spare Glass (pk 5)

*Max. current must be externally limited


SU0631 Manual Call Point

The SU0631 Manual Call Point is supplied with one normally open and one normally closed contact. Selecting either the “Normally Open” or “Normally Closed” contact is easily achieved by simply connecting the terminal block to the required connection in the back of the MCP. Single pole changeover switching can be achieved with the use of two terminal blocks. The Call Point and Backbox are ordered separately. The call point is operated when the frangible glass element is snapped, releasing the MCP’s micro switch, which signals an alarm to the fire panel.

Specifications

  • Max. Operating Voltage 30Vdc
  • Max. Switch Current 2A
  • Cable Termination 0.5 to 2.5 mm2
  • Relative Humidity 0 to 95% (non/cond)
  • Ambient Temperature -10°C to +55°C
  • Weight 110g (flush)
  • Ingress Protection IP24D

Part Numbers

  • SU0631 Manual Call Point
  • SU0632 Red Backbox
  • SU0615 Transparent Hinged Cover
  • SC070 Spare Test Keys (pkt10)
  • 515.001.025 Spare Glass (pkt 5)
  • See page 12 for MCP accessories

4099-9032 Manual Call Point

The 4099-9032 addressable Manual Call Point (MCP) provides a means to manually initiate a fire alarm condition to the 4100U c.i.e. via the IDNet channel. The IDNet channel provides the communication link and power between the call point and 4100U. Activation of the MCP requires the frangible element to be broken, which causes contacts on a microswitch to close, initiating an alarm condition. Call Point reset requires the fitting of a replacement frangible element. The MCP features an integral red LED status indicator. The Simplex 4099-9032NL MCP is connected to Simplex c.i.e. via MAPNET II and does not have a status indicator.

Specifications

  • Comms Power1 24 to 40Vdc w/data
  • Dimensions (HWD) 86x87x35mm
  • Ambient Temperature -9°C to +70°C
  • Relative Humidity 10% to 95% (n/c)
  • CSIRO ActivFire listed afp-1691

Part Numbers

  • 4099-9032 IDNet & red LED
  • 4099-9032N MAPNET II, no LED
  • 515.001.025 Spare Glass (pk 5)
  • SR3T-P Backbox c/w Terminals

1. MAPNET II or IDNet communications with data


SU0608 Evacuation Manual Call Point

The SU0608 MCP is surface mounting, with a plastic coated glass element to ensure reliable, safe operation. It is coloured white (for EWIS applications) to be used where a fire alarm system does not exist. The call point is operated when the glass element is snapped, releasing the MCP’s micro switch, which signals an alarm to the EWIS panel. The element is snapped by pressing on its centre – a hammer, or other impact device, is not required.

Specifications

  • Max Current Resistive 8A @ 30Vdc
  • Inductive 3A @ 30Vdc
  • Contact Resistance 100mOhm. (max)
  • Legend Emergency Alarm
  • Ambient Temp -30 to +70°C
  • Relative Humidity 95%(non cond.)

Part Numbers

  • SU0608 White MCP & Backbox
  • 515.001.025 Spare Glass (pk 5)

SU0611 Waterproof Callpoint

This surface mounting Manual Call Point has a plastic coated frangible element to ensure safe and reliable operation, producing no dangerous glass shards. The SU0611 is an IP67 rated MCP wih a single pole changeover switch configuration. SU0611 is operated by simply pressing on the centre of the frangible element until it snaps. A hammer, or other impact device, is not required. The snapped frangible element releases a microswitch, which signals an alarm at the CIE. It carries LPCB approval.

Specifications

  • Operating Voltage 230VAC (max.)
  • Operating Current 3A @ 230VAC (max.)
  • Dimensions (HWD) 125x125x80 mm
  • Ingress Protection IP67
  • Not CSIRO ActivFire listed by Tyco

Part Numbers

  • SU0611 MCP
  • 515.001.025 Spare Glass (pk 5)
  • SU0622 Gasket Pack of 5

SU0612 Rainproof Callpoint

This surface mounting Manual Call Point has a plastic coated frangible element to ensure safe and reliable operation, producing no dangerous glass shards. The callpoint is operated by simply pressing on the centre of the frangible element until it snaps. A hammer, or other impact device, is not required. The snapped frangible element releases a microswitch, which signals an alarm at the CIE. The SU0612 provides IP55 protection for the terminal enclosure and IP55 for the switch. Ex rated devices are available. Contact TSP.

Specifications

  • Operating Voltage 230VAC (max.)
  • Operating Current 3A @ 230VAC (max.)
  • Dimensions (HWD) 123x123x80 mm
  • Ingress Protection IP55
  • Not CSIRO ActivFire listed by Tyco

Part Numbers

  • SU0612 MCP
  • 515.001.025 Spare Glass (pk 5)
  • SU0623 Gasket Pack of 5

Weather STOPPER


The callpoint STOPPER provides protection from malicious or accidental activation of manual callpoints. Available for flush or surface mounted callpoints the ‘STOPPER’ is also available with optional high pitch sounder which is activated when the lid is lifted. An optional ‘Break-Seal’ fitting kit allows ‘Break-Seals’ to be used to provide extra protection.

Specifications

  • STI6535 STI3150
  • Dims (HWD) 210x137x57.5 254x178x86
  • Call Point Size 100x100x57.5 160x160x120
  • Ingress Protection Weatherproof

Part Numbers

  • 515.001.033 IP036 Break Seal Kit
  • 515.001.032 STI6533 Surface fit Weather STOPPER with sounder
  • 515.001.035 STI3150 Weather Stopper II
  • 515.001.036 STI6535 Weather Stopper

Weather STOPPER II

The Weather STOPPER II extends the life of weather exposed callpoints, by offering protection against harsh conditions and environments, eg, oil rigs and ship decks. While offering environmental protection the Weather STOPPER II are constructed from polycarbonate which will also guard against tampering or accidental operation of devices.


Manual Call Point Ancillaries

Part Numbers

  • SU0605 Spare glasses, WORMALD white English text on clear background (Pack 10)
  • 515.001.025 Spare glasses, clear text on white
    background, no logo (Pack 5)

Part Number

  • SU0632 Standard Red surface mounting back box for CP200/500 & 900 indoor callpoints

Part Number

  • SC070 Packet of ten Test keys for Tyco indoor MCPs (SU0601 & SU0631)

Part Number

  • SU0615 Transparent hinged cover to suit all SUxxx callpoints (MCP not included)

Part Number

  • SR3T-P Red surface mounting back box (for indoor callpoints) with terminals fitted.

Part Number

  • 515.001.026 Black callpoint bezel for Tyco CP200/500/900